Carbon Dioxide Detection Tubes 5%/A (5 - 60 Vol%)
For short-term measurements more than 160 Draeger-Tubes are available to measure the spot concentrations of specific gases. Measurement usually takes between 4 seconds and 15 minutes. The tubes are used either manually with the Draeger-Tube Accuro Pump or automatically with the Draeger X-act 5000.
A wide range of different gases and vapours can be detected and measured, such as:
- Determining and measuring concentration peaks
- Measuring personal exposure in the inhalation area
- Detecting leaks in pipelines, gas installations etc.
- Air analysis in sewers, shafts and confined spaces.
Carbon Dioxide Detection Tubes 5%/A (5 - 60 Vol%)
Standard Measuring Range: |
5 to 60 Vol. % |
Number of Strokes (n): |
1 |
Time for Measurement: |
approx. 2 min. |
Standard Deviation: |
± 10 to 15 % |
Color Change: |
white ?> violet |
Temperature: |
0 to 40° C |
Absolute Humidity: |
max. 50 mg H2O / L |
Reaction Principle: |
CO2 + N2H4?> NH2-NH-COOH |
Cross Sensitivity: |
Hydrogen sulphide is not indicated near the limit value. Sulfur dioxide is indicated with approx. half sensitivity |
Carbon Dioxide Detection Tubes 5%/A (5 - 60 Vol%)