Tetrahydrothiophene Detection Tubes 1/b (1 - 10 ppm)
For short-term measurements more than 160 Draeger-Tubes are available to measure the spot concentrations of specific gases. Measurement usually takes between 4 seconds and 15 minutes. The tubes are used either manually with the Draeger-Tube Accuro Pump or automatically with the Draeger X-act 5000.
A wide range of different gases and vapors can be detected and measured, such as:
- Determining and measuring concentration peaks
- Measuring personal exposure in the inhalation area
- Detecting leaks in pipelines, gas installations etc.
- Air analysis in sewers, shafts and confined spaces
Tetrahydrothiophene Detection Tubes 1/b (1 - 10 ppm)
Standard Measuring Range: |
1 to 10 ppm / 4 to 40 mg/m3 |
Number of strokes n: |
30 |
Time for Measurement: |
in air: approx. 15 min in natrual gas: approx. 10 min |
Standard Deviation: |
15 to 20 % |
Color Change: |
violet ??> yellow brown |
Temperature: |
0 to 35 °C |
Absolute Humidity: |
< 30 mg H2O / L |
Reaction Principle: |
THT + KMnO4 ??> yellow brown reaction product |
Cross Sensitivity: |
Up to 10 ppm hydrogen sulfide is adsorbed in the pretube, causing a brown discoloration. It is impossible to measure tetrahydrothiophene in the presence of mercaptans. Up to 100 ppm of olefines (e. g. ethene, propene) will cause the color of the indicating layer to become lighter, at higher concentrations the olefins are also indicated. Up to 200 ppm methanol does not interfere. |
Extension of Measuring Range: |
1.6 to 16 ppm / 6.4 to 64 mg/m3
n = 20 multiply the reading by 1.6 |
Tetrahydrothiophene Detection Tubes 1/b (1 - 10 ppm)