Hydrogen Sulfide (H2S) Detection Tubes (1 to 40%)
Gastec Detection Tube No. 4HT measures Hydrogen Sulfide with a Range of 1 to 40%.
- Measuring Range:
- 1 to 2%
- 2 to 20%
- 20 to 40%
- Number of Pump Strokes: 2, 1, 1/2
- Correction Factor: 1/2, 1 , 2
- Sampling Time: 1.5 minutes per pump stroke
- Detecting Limit: 0.2% (2 pump strokes)
- Changes from Pale Blue to Blackish Brown
- Corrections for temperature & humidity: Unnecessary
- 3 Year Shelf Life
- Reaction Principle: H2S + CuSO4 → CuS + H2SO4
- Relative standard deviation: 10% (for 2 to 6 %), 5% (for 6 to 20 %)
- Store the tubes at cool and dark place.
Possible coexisting substances and their interferences:
Substance |
Concentration |
Interference |
Changes color by itself to |
Mercaptans |
≧ 10% |
+ |
No |
Sulfur dioxide |
≧ 5% |
- |
No |
Hydrogen Sulfide (H2S) Detection Tubes (1 to 40%)
There are no reviews yet.